General data
Operating voltage range: 10–30 V DC.
Nominal input voltage: ~24 V DC.
Isolation: 250 V continuous (basic insulation between input‑to‑backplane and group‑to‑group).
Diagnostic per-point: wire‑off detection.
Diagnostic timestamp resolution: ±1 ms.
Backplane / module interface: fits 1756 ControlLogix chassis.
Terminal block: compatible with 1756‑TBNH or 1756‑TBSH.
Power dissipation: up to ~5.8 W at 60 °C.