Isolation voltage: 250 V continuous, between output groups and backplane.
Surge current: up to 4 A for 10 ms; continuous current: 2 A @ 60 °C.
Diagnostic features: no‑load detection, output state verification via pulse testing, per-point electronic fusing.
Operating temperature: 0 °C to 60 °C.
Backplane current: ~250 mA @ 5 V, ~140 mA @ 24 V.
Compatible removable terminal blocks: 1756‑TBCH or 1756‑TBS6H.
Certifications: UL, CE, etc., per ControlLogix I/O spec sheet.
Fichas técnicas
-
H&DAutomatisierungstechnik
Allen‑Bradley 1756‑OB16D ControlLogix 16‑Point Diagnostic DC Output Module
16 diagnostic DC outputs; 19.2–30 V DC output voltage; 1 A per point; 8 A module max at 30 °C, 4 A at 60 °C.
Allen‑Bradley / Rockwell Automation
New
No se pudo cargar la disponibilidad de retiro
Emitimos una factura con IVA desglosado para cada compra. Los clientes internacionales fuera de Alemania están exentos del IVA. Tenga en cuenta que nuestra venta internacional se realiza exclusivamente a clientes empresariales. Por favor, indique su ID de IVA al comprar. El envío se realiza normalmente con DHL dentro de Alemania y con DHL Express al extranjero.